TRANSMISSION ROUTES IMPORTANT FOR EVERY EPIDEMIC ARE THE TRANSMISSION ROUTES OF THE INFECTIOUS AGENT.
In relation to
COVID19 the standard assumption is that the following two transmission routes
are dominant: via large droplets (droplets/particles emitted when sneezing or
coughing or talking) and via surface (fomite) contact (hand-hand, hand-surface
etc.). A third transmission route that is gaining more attention from the
scientific community is the faecal-oral route. The faecal-oral transmission
route for SARS-CoV-2 infections is implicitly recognized by WHO, see their
latest technical briefing of March 2, 2020. In this document they propose as
precautionary measure to flush toilets with closed lid. Additionally, they
suggest avoiding dried-out drains in floors and other sanitary devices by
regularly adding water (every 3 weeks depending on climate) so that the water
seal works properly. This is in line with an observation during the SARS
2003-2004 outbreak: open connections with sewage systems appeared to be a
transmission route in an apartment building in Hong Kong (Amoy Garden). It is
known that flushing toilets are creating plumes containing droplets and droplet
residue when toilets are flushed with open lids. And we know that SARS-CoV-2
viruses have been detected in stool samples (reported in recent scientific
papers and by the Chinese authorities). In addition, a comparable incident was
recently reported in an apartment complex (Mei House). Therefore, the
conclusion is that the faecal-oral transmission routes can’t be excluded as
transmission route. Via air there are two exposure mechanisms: 1. Close contact
transmission through large droplets (> 10 microns), which are released and
fall to surfaces not further than about 1-2 m from the infected person. Droplets
are formed from coughing and sneezing (sneezing forms many more particles
typically). Most of these large droplets fall on nearby surfaces and objects –
such as desks and tables. People could catch the infection by touching those
contaminated surfaces or objects; and then touching their eyes, nose or mouth.
If people are standing within 1-2 meter of an infected person, they can catch
it directly by breathing in droplets sneezed or coughed out or exhaled by them.
2. Airborne transmission through small particles (< 5 microns), which may
stay airborne for hours and can be transported long distances. These are also
generated by coughing and sneezing and talking. Small particles (droplet nuclei
or residue) form from droplets which evaporate (usually within milliseconds)
and desiccate. The size of a coronavirus particle is 80-160 nanometre2 and it
remains active at common indoor conditions up to 3 hours in indoor air and 2-3
days on room surfaces (unless there is specific cleaning). Such small virus
particles stay airborne and can travel long distances carried by airflows in
the rooms or in the extract air ducts of ventilation systems. Airborne
transmission has caused infections of SARS-CoV-1 in the past; currently there
is no reported evidence yet specifically for Corona disease (COVID-19)
infection via this route. There is also no reported data or studies to rule out
the possibility of the airborne-particle route. One indication for this: Corona
virus SARS-CoV-2 has been isolated from swabs taken from exhaust vents in rooms
occupied by infected patients. This mechanism implies that keeping 1-2 m
distance from infected persons might not be enough and increasing the
ventilation is useful because of removal of more particles.
With
SARS-CoV-2 the airborne route – infection through exposure to droplet nuclei
particles – has not been demonstrated but may exist when certain conditions are
met (i.e. opportunistic airborne) according to Chine national Health Commission
(unpublished result). Conclusion in relation to the airborne transmission
route: At this date we need all efforts to manage this pandemic from all
fronts. Therefore REHVA proposes, especially in ‘hot spot’ areas to use the
ALARA principle (As Low As Reasonably Achievable) and to take a set of measures
that help to also control the airborne route in buildings (apart from standard
hygiene measures as recommended by WHO, see the ‘Getting workplaces ready for
COVID-19’ document).
Practical recommendations for building services operation
Increase air
supply and exhaust ventilation In buildings with mechanical ventilation systems
extended operation times are recommended. Change the clock times of system
timers to start ventilation a couple of hours earlier and switch off later than
usual. Better solution is even to keep the ventilation on 24/7, possibly with
lowered (but not switched off) ventilation rates when people are absent.
Considering a springtime with small heating and cooling needs, the
recommendations above have limited energy penalties, while they help to remove
virus particles out of the building and to remove released virus particles from
surfaces. The general advice is to supply as much outside air as reasonably
possible. The key aspect is the amount of fresh air supplied per person. If,
due to smart working utilization, the number of employees is reduced, do not
concentrate the remaining employees in smaller areas but maintain or enlarge
the spacing among them in order to foster the ventilation cleaning effect.
Exhaust ventilation systems of toilets should always be kept on 24/7, and make
sure that underpressure is created, especially to avoid the faecal-oral
transmission.
Use more
window airing General recommendation is to stay away from crowded and poorly
ventilated spaces. In buildings without mechanical ventilation systems it is
recommended to actively use operable windows (much more than normally, even
when this causes some thermal discomfort). Window airing then is the only way
to boost air exchange rates. One could open windows for 15 min or so when
entering the room (especially when the room was occupied by others beforehand).
Also, in buildings with mechanical ventilation, window airing can be used to
further boost ventilation. Open windows in toilets with passive stack or
mechanical exhaust systems may cause a contaminated airflow from the toilet to
other rooms, implying that ventilation begins to work in reverse direction.
Open toilet windows then should be avoided. If there is no adequate exhaust
ventilation from toilets and window airing in toilets cannot be avoided, it is
important to keep windows open also in other spaces in order to achieve cross
flows throughout the building. Humidification and air-conditioning have no
practical effect Transmission of some viruses in buildings can be limited by
changing air temperatures and humidity levels. In the case of COVID-19 this is
unfortunately not an option as the SARS-CoV-2 virus is quite resistant to
environmental changes and is susceptible only for a very high relative humidity
above 80% and a temperature above 30 ˚C, which are not attainable and
acceptable in buildings for other reasons (e.g. thermal comfort). Small
droplets under interest (0.5 – 10 micron) will evaporate fast under any
relative humidity (RH) level. Nasal systems and mucous membranes are more
sensitive to infections at very low RH of 10-20 %, and this is the reason for
which some humidification in winter is sometimes suggested (up to a level of
about 30%). This indirect need for humidification in the COVID-19 case is not
relevant however given the incoming climatic conditions (from March onwards we
expect indoor RH higher than 30% in all European climates without
humidification). Thus, there is no need to change humidification systems’ setpoints.
Considering the springtime that is about to start, these systems should not be
in operation anyhow. Heating and cooling systems can be operated normally as
there are no direct implications on COVID19 spread. Usually, any adjustment of
setpoints for heating or cooling systems is not needed. Safe use of heat
recovery sections Under certain conditions virus particles in extract air can
re-enter the building. Heat recovery devices may carry over virus attached to
particles from the exhaust air side to the supply air side via leaks. In rotary
heat exchangers (including enthalpy wheels) particles deposit on the return air
side of the heat exchanger surface after which they might be resuspended when
heat exchanger turns to the supply air side. Therefore, it is recommended to
(temporarily) turn off rotary heat exchangers during SARS-CoV-2 episodes. If
leaks are suspected in the heat recovery sections, pressure adjustment or
bypassing can be an option in order to avoid a situation where higher pressure
on extract side will cause air leakages to supply side. Virus particle
transmission via heat recovery devices is not an issue when a HVAC system is
equipped with a twin coil unit or another heat recovery device that guarantees
100% air separation between return and supply side. No use of recirculation
Virus particles in return ducts can also re-enter a building when centralized
air handling units are equipped with recirculation sectors. It is recommended
to avoid central recirculation during SARSCoV-2 episodes: close the
recirculation dampers (via the Building Management System or manually). In case
this leads to problems with cooling or heating capacity, this has to be
accepted because it is more important to prevent contamination and protect
public health than to guarantee thermal comfort.
Sometimes air
handling units and recirculation sections are equipped with return air filters.
This should not be a reason to keep recirculation dampers open as these filters
normally do not filter out particles with viruses effectively since they have
standard efficiencies and not HEPA efficiencies. When possible, decentralized
systems such as fan coil units that use local recirculation, also should be
turned off to avoid resuspension of virus particles at room level (esp. when rooms
are used normally by more than one occupant). Fan coil units have coarse
filters which practically do not filter out particles with viruses. If not
possible to turn off, these units are to be included into cleaning campaigns,
because they might collect particles as any other surface in the room. Duct
cleaning has no practical effect There have been overreactive statements
recommending to clean ventilation ducts in order to avoid SARS-CoV-2
transmission via ventilation systems. Duct cleaning is not effective against
room-to-room infection because the ventilation system is not a contamination
source if above guidance about heat recovery and recirculation is followed.
Viruses attached to small particles will not deposit easily in ventilation
ducts and normally will be carried out by the air flow anyhow. Therefore, no
changes are needed to normal duct cleaning and maintenance procedures. Much
more important is to increase fresh air supply, avoid recirculation of air
according to the recommendations above. Change of outdoor air filters is not
necessary In COVID-19 context, it has been asked should the filters to be
replaced and what is the protection effect in very rare occasions of outdoor
virus contamination, for instance if air exhausts are close to air intakes.
Modern ventilation systems (air handling units) are equipped with fine outdoor
air filters right after the outdoor air intake (filter class F7 or F83 or ISO
ePM1) which filtrate well particulate matter from outdoor air. The size of a
coronavirus particle of 80-160 nm (PM0.1) is smaller than the capture area of
F8 filters (capture efficiency 65-90% for PM1), but many of such small
particles will settle on fibres of the filter by diffusion mechanism.
SARS-CoV-2 particles also aggregate with larger particles which are already
within the capture area of filters. This implies that in rare cases of virus
contaminated outdoor air, fine outdoor air filters provide a reasonable
protection for a low concentration and occasionally spread viruses in outdoor
air. From the filter replacement perspective, normal maintenance procedures can
be used. Clogged filters are not a contamination source in this context, but
they reduce supply airflow which has a negative effect on indoor contaminations
itself. Thus, filters must be replaced according to normal procedure when
pressure or time limits are exceeded, or according to scheduled maintenance. In
conclusion, we do not recommend changing existing outdoor air filters and
replace them with other type of filters nor do we recommend changing them
sooner than normal. Room air cleaners can be useful in specific situations Room
air cleaners remove effectively particles from air which provides a similar
effect compared to ventilation. To be effective, air cleaners need to have at least
HEPA filter efficiency. Unfortunately, most of attractively priced room air
cleaners are not effective enough. Devices that use electrostatic filtration
principles (not the same as room ionizers!) often work quite well too. Because
the airflow through air cleaners is limited, the floor area they can
effectively serve is normally quite small, typically less than 10 m2 . If one
decides to use an air cleaner (again: increasing regular ventilation often is
much more efficient) it is recommended to locate the device close to the
breathing zone. Special UV cleaning equipment to be installed for the supply
air or room air treatment is also effective as killing bacteria and viruses but
this is normally only a suitable solution for the equipment for health care facilities.
Toilet lid use instructions If toilet
seats are equipped with lids it is recommended to flush the toilets with closed
lids in order to minimize the release of droplets and droplet residues from
plumes in the air. It is important that water seals work all time. Therefore,
organise that building occupants are instructed to use the lids.
Colophon This document was prepared by a group of REHVA
volunteers in the period March 6-15th 2020. Members of the expert group are:
Prof. Jarek Kurnitski, Tallinn University of Technology, Chair of REHVA
Technology and Research Committee Atze Boerstra, REHVA vice-president, managing
director bba binnenmilieu Francesco Franchimon, managing director Franchimon
ICM Prof. Livio Mazzarella, Milan Polytechnic University Jaap Hogeling,
managing director ISSO international project Frank Hovorka, REHVA president,
director technology and innovation FPI, Paris Prof. em. Olli Seppänen, Aalto
University The draft document of the paper was reviewed by Prof. Yuguo Li from
the University of Hongkong and Prof. Shelly Miller from the University of
Colorado Boulder.
Literature
This document is partly based on a literature survey, the scientific papers and
other documents that were used can be found in this document:
https://www.rehva.eu/fileadmin/user_upload/REHVA_COVID19_guidance_document_Bibliography.pdf
Σχόλια